How to classify the seasonal energy efficiency ratio of air conditioning systems?

Nov 09,2026

How to classify the seasonal energy efficiency ratio of air conditioning systems?

I. distinguish between several seasonal energy efficiency indicators (generally used for heating).

SEER: Seasonal Energy Efficiency Ratio for Cooling (Inverter Wall-Mounted/Floor-Mounted Units) , GB21455-2019, Level 1 is the highest , the higher the number, the more energy-efficient.

APF: Annual Energy Efficiency (for heat pump room air conditioners that cover both cooling and heating seasons) . Currently, the APF is the main indicator for the labeling of inverter air conditioners that support both cooling and heating.

IPLV (C): Integrated Part Load Factor for Cooling (VRF for Multi-Split Units, Chillers) , for commercial central air conditioning systems. It is not SEER, but belongs to the seasonal/part load energy efficiency index.

HSPF: Seasonal Energy Efficiency Ratio (Heat Pump Heating Season).

Note: For fixed-frequency room air conditioners, SEER is not assessed; rated EER is used instead . SEER is a seasonal indicator for variable-frequency models.

 


II. Split-type single-cooling air conditioner for the room, SEER rating (GB21455 2019, Level 5)

Rated cooling capacity (CC)

Level 1 SEER

Level 2 SEER

Level 3 SEER

Level 4 SEER

Level 5 SEER

≤4500W (1.5 horsepower and below)

≥5.80

≥5.40

≥5.00

≥3.90

≥3.70

4500<CC≤7100W (2 horses)

≥5.50

≥5.10

≥4.40

≥3.80

≥3.60

7100<CC≤14000W (3 horses)

≥5.20

≥4.70

≥4.00

≥3.70

≥3.50

Heat pump room air conditioners (cooling and heating type): do not use SEER classification, but APF classification , also level 5.

III. Multi-split air conditioner (VRF, GB21454 2021)

Air-cooled multi-split air conditioner:

Cooling-only type: Classified by SEER (Grade 1/2/3)

Heating and cooling heat pump type: using APF

Water-cooled multi-split air conditioners: classified by IPLV(C) (Level 1/2/3)

 


IV. Water chillers and air-cooled modular chillers (GB19577)

Using IPLV (Integrated Partial Load), it is divided into three levels: 1, 2, and 3 , and SEER is no longer used; level 1 is optimal.

V. A Simple Understanding of the Logic of Division

1. The smaller the energy efficiency rating, the higher the efficiency: Level 1 > Level 2 > Level 3 > Level 4 > Level 5;

2. SEER is the weighted average energy efficiency under different outdoor temperatures and loads throughout the entire cooling season, which is closer to real-world power consumption than the rated EER;

3. For residential wall-mounted and floor-standing air conditioners: For single-cooling inverters, consider SEER; for cooling and heating inverters, consider APF.

4. Commercial multi-split air conditioners and chillers: See IPLV (C) / IPLV (H).

 


VI. The difference between 14 SEER and 16 SEER

In short: 14 SEER and 16 SEER are the American standard for seasonal energy efficiency ratio (SEER) , which is mostly used in American ducted central air conditioning (split-type air-cooled cabinet units and rooftop units). They are not the Chinese national standard SEER (GB) , and cannot be directly compared with domestic air conditioner labels.

1. Definition

SEER = Total cooling capacity for the entire cooling season (BTU) ÷ Total electricity consumption for the season (Wh)

14 SEER : On average, it produces 14 BTU of cooling capacity for every 1Wh of electricity consumed.

16 SEER : On average, it produces 16 BTU of cooling capacity for every 1Wh of electricity consumed. The higher the number, the more energy-efficient it is in different seasons.

2. Comparison of 14 vs 16

For the same cooling capacity: Power consumption ratio = 14 ÷ 16 = 0.875 , 16SEER saves approximately 12.5% more energy than 14SEER.

14 SEER: American entry-level qualified models, mostly single-stage constant-volume compressors, and inexpensive.

16 SEER: Mainstream medium- and high-efficiency models, many of which are two-stage compressors/variable capacity models , with better temperature control and dehumidification , but at a higher cost.

 


3. Key pitfalls (make sure to distinguish them when selecting HVAC systems)

The US standard SEER is not the same as the domestic GB21455 SEER . The testing conditions are completely different, so they cannot be directly equated. The highest SEER for a 1.5 HP inverter in China is only 5.8, which is not the same system as the US standard SEER of more than 10.

SEER2 standard after 2023 , with more stringent testing:

14 SEER (old standard) ≈ 13.4 SEER2

16 SEER (old standard) ≈ 15.2 SEER2

SEER only considers the cooling season and does not include heating; for heat pump cooling and heating systems, the US standard is based on HSPF (heating season energy efficiency).

4. Simple Selection Reference

Short cooling time and cheap electricity: Choose 14 SEER for a short payback period; Hot regions with long annual cooling time and high electricity prices: Prioritize 16 SEER for longer-term electricity savings.